Getting Started

[简体中文]

[toc]

Hardware Connection

Power input and output

The voltage range is 4.5~50V, and the output is as much as the input.

RS485 to RS485

All RS485 interfaces are connected, you can freely choose one RS485 interface access, and choose another RS485 interface output.

4~20mA/1~5V to RS485

  1. When you receive 4~20mA signal, you need to set the switch to “I”; when you receive 1~5V signal, then set the switch to “*** V***”.

  2. 4~20mA/1~5V sensors are accessed from Analog_In and Analog_GND and output to Sensor_Hub/Wireless_ Aggregator from any RS485 interface.

Dataframe Description

Description

  • Baud Rate: 9600

  • Serial Port: 8N1

  • Dataframe: 0x66(Slave address) 0x09(FUNC) 0x00 0x00(Begin address, 2Byte) 0x00 0x00 (Number of registers, 2byte) CRC16 (CRC Checksum 2Byte)

Type

Address

Name

Quantity

Register Status

Resolution

INPUT REGISTER

0x0000

4~20 mA

2

Read-only

1 ua

INPUT REGISTER

0x0002

1~5 V

2

Read-only

1 mv

  • Negative: -1 == 0xFFFFFFFF; -2==0XFFFFFFFE;

Example

Reading voltage

  • Send: 66 09 00 02 00 02 F5 DD

  • Rec: 66 09 00 00 0E 0B 90 7B

0X00000E0B => 3595 mV

Reading current

  • Send: 66 09 00 00 00 02 54 1D

  • Rec: 66 09 00 00 17 70 DB C8

0X00001770 => 6000 uA

Actual error test

1~5V

Input(mV)

Reading(mV)

Error value(mV)

1000

998

2

2000

1996

4

3000

2995

5

4000

3992

8

5000

4988

12

4~20mA

Input(uA)

Reading(uA)

Error value(uA)

4000

4001

1

6000

5997

3

8000

7995

5

10000

9991

9

12000

12007

7

14000

14005

5

16000

16005

5

18000

18002

2

20000

19998

2